Check The Charge Without Connecting Gauges - Part 2
HVAC School - For Techs, By Techs · Bryan Orr
June 14, 201754m 17s
Audio is streamed directly from the publisher (traffic.libsyn.com) as published in their RSS feed. Play Podcasts does not host this file. Rights-holders can request removal through the copyright & takedown page.
Show Notes
In this second part of the podcast, Jim Bergmann wraps up the steps to check a system charge without connecting a gauge manifold.
You can check the charge without gauges if you use the following process (and know your DTD, CTOA, etc.):
- Take the dry-bulb temperature. (Let's say it's 70°F in this example.)
- Subtract the DTD (35°F).
- Add target superheat (10°F).
- Check the suction line. It should be 45°F in this example. If your probe senses a temperature that is NOT within 5°F of the temperature you calculated, check the filter, evaporator coil, etc., for dirt.
- If the system is not dirty, check the charge with gauges.
For a more extensive look at the process in writing, check out THIS article.